Model no
8Al Basic Analog Input Module for VoltageArticle No
P7 134-6FF00-0AA1Description
AI 8xU BAModule Width
15mm| Specification parameters | Model | 8Al Basic Analog Input Module for Voltage |
| Article No | P7 134-6FF00-0AA1 | |
| Description | AI 8xU BA |
| Standard | Supply Voltage | Rated Value (DC):24 V Permissible Lower Limit (DC): 19.2 V Permissible Upper Limit (DC): 28.8 V |
| Reverse Polarity Protection | √ | |
| Power consumption, Typ | 0.7 W | |
| Environmental Conditions | ||
| .STEP 7 TlA Portal | V13 SP1 and higher | |
| .STEP 7 V5.5 | SP3 and higher | |
| Number of analog input channels | 8 | |
| Input signal type (resolution) | 0 to+10V (15 digits) -10V to+10V (16 bits including sign bit) |
|
| Interference suppression frequency | 16.67/50/60/4800Hz | |
| Conversion time (per channel) | 180/60/50/0.625ms | |
| Smoothing level | None, 4, 8, 16 times | |
| Shielded cable length, max | 200 m | |
| Basic accuracy (at 25 ℃) | ±0.3% | |
| Full temperature range accuracy (-30 ℃ to 60 ℃) | ±0.5% | |
| Base unit | A0, A1 | |
| Diagnostic interruption | √ | |
| Diagnostic function | • Power supply voltage monitoring • configuration error • Overflow/underflow |
|
| Isolation between channel and backplane bus | √ | |
| Operating Ambient Temperature | Horizontal Mounting, Min: -30°C Horizontal Mounting,Max: 60°C Vertical Mounting, Min: -30°C Vertical Mounting, Max: 50°C |
|
| Module Width | 15mm |