Model no
4Al Standard Analog Input Module for CurrentArticle No
P7 134-6GD01-0BA1Description
AI 4xI 2-/4-wire STModule Width
15mm| Specification parameters | Model | 4Al Standard Analog Input Module for Current |
| Article No | P7 134-6GD01-0BA1 | |
| Description | AI 4xI 2-/4-wire ST |
| Standard | Supply Voltage | Rated Value (DC):24 V Permissible Lower Limit (DC): 19.2 V Permissible Upper Limit (DC): 28.8 V |
| Reverse Polarity Protection | √ | |
| Power consumption, Typ | 0.85 W | |
| Environmental Conditions | ||
| .STEP 7 TlA Portal | V14 and higher | |
| .STEP 7 V5.5 | V5.6 and higher | |
| Number of analog input channels | 4 | |
| Input signal type (resolution) | 0 to 20mA (15 bits) 4 mA to 20 mA (15 bits) -20mA to+20mA (15 bits including symbol) |
|
| Conversion time (per channel) | 180/60/50 ms | |
| Suppression frequency | 16.6/50/60 Hz | |
| Shielded cable length, max | 1000 m | |
| Smoothing level | None, 4, 8, 16 times | |
| Base Unit | A0 A1 | |
| Diagnostic Interrupt | √ | |
| Diagnostic Functions | • Power supply voltage monitoring • Disconnected (4 to 20 mA) • Short circuit (2-wire) • Accumulated faults • Overflow/underflow |
|
| Basic accuracy (at 25 ℃) | ±0.3% | |
| Full temperature range accuracy (-30 ℃ to 60 ℃) | ±0.5% | |
| Isolation between channel and backplane bus | √ | |
| Isolation between channels | √ | |
| Operating Ambient Temperature | Horizontal Mounting, Min: -30°C Horizontal Mounting,Max: 60°C Vertical Mounting, Min: -30°C Vertical Mounting, Max: 50°C |
|
| Module Width | 15mm |