banner
Home   -   Product  -   PLC  -   Remote IO  -   HD 200SP

4Al Standard Analog Input Module for Voltageand Current

AI 4xU/I 2-wire ST

Model no

4Al Standard Analog Input Module for Voltageand Current

Article No

P7 134-6HD01-0BA1

Description

AI 4xU/I 2-wire ST

Module Width

15mm
Product parameters Wiring diagram Relevant information
Specification parameters Model 4Al Standard Analog Input Module for Voltageand Current
Article No P7 134-6HD01-0BA1
Description AI 4xU/I 2-wire ST
Standard Supply Voltage Rated Value (DC):24 V
Permissible Lower Limit (DC): 19.2 V
Permissible Upper Limit (DC): 28.8 V
Reverse Polarity Protection
Power consumption, Typ 0.85 W
Environmental Conditions
   .STEP 7 TlA Portal  V14 and higher
   .STEP 7 V5.5 V5.5 SP3 and higher
Number of analog input channels 4
Input signal type (resolution) ± 5V (16 bits including symbol)
± 10V (16 bits including symbol)
1 to 5V (15 bits)
0 to 10V (15 digits)
0mA to 20mA (15 bits)
4mA to 20mA (15 bits)
Conversion time (per channel) 180/60/50 ms
Suppression frequency 16.6/50/60 Hz
Shielded cable length, max 1000 m; voltage signal 200 m
Smoothing level None, 4, 8, 16 times
Base Unit A0 A1
Diagnostic Interrupt
Diagnostic Functions • Power supply voltage monitoring
• Disconnected (4 to 20 mA)
• Short circuit (when 1 to 5V or 2-wire)
• Accumulated faults
• Overflow/underflow
Basic accuracy (at 25 ℃) Voltage: ± 0.3%
Current: ± 0.3%
Full temperature range accuracy (-30 ℃ to 60 ℃) Voltage: ± 0.5%
Current: ± 0.5%
Isolation between channel and backplane bus
Isolation between channels
Operating Ambient Temperature Horizontal Mounting, Min: -30°C
Horizontal Mounting,Max: 60°C
Vertical Mounting, Min: -30°C
Vertical Mounting, Max: 50°C
Module Width 15mm