Model no
4AO Standard Analog Output ModuleArticle No
P7 135-6HD00-0BA1Description
AQ 4xU/I STModule Width
15mm| Specification parameters | Model | 4AO Standard Analog Output Module |
| Article No | P7 135-6HD00-0BA1 | |
| Description | AQ 4xU/I ST |
| Standard | Supply Voltage | Rated Value (DC):24 V Permissible Lower Limit (DC): 19.2 V Permissible Upper Limit (DC): 28.8 V |
| Reverse Polarity Protection | √ | |
| Power consumption, Typ | 1.5 W | |
| Environmental Conditions | ||
| .STEP 7 TlA Portal | V11 SP2 and higher / V13 | |
| .STEP 7 V5.5 | SP3 and higher | |
| Number of analog output channels | 4 | |
| Voltage output range (resolution) | 0 to 10V (15 digits) 1 to 5V (13 bits) -5 to+5V (15 bits including sign bit) -10 to+10V (16 bits including sign bit) |
|
| Current output range (resolution) | 0 to 20mA (15 bits) -20 to+20mA (16 bits including sign bit) 4 to 20mA (14 bits) |
|
| Conversion time (per channel) | Min 5 ms | |
| Basic accuracy (at 25 ℃) | Voltage: ± 0.3% Current: ± 0.3% |
|
| Full temperature range accuracy (0 ℃ to 60 ℃) | Voltage: ± 0.5% Current: ± 0.5% |
|
| Shielded cable length, max | 1000 m; voltage signal 200 m | |
| Base unit | A0, A1 | |
| Diagnostic interruption | √ | |
| Diagnostic function | • Power supply voltage monitoring • Open circuit • Short circuit • Overflow/underflow |
|
| Isolation between channel and backplane bus | √ | |
| Operating Ambient Temperature | Horizontal Mounting, Min: -30°C Horizontal Mounting,Max: 60°C Vertical Mounting, Min: -30°C Vertical Mounting, Max: 50°C |
|
| Module Width | 15mm |