banner
Home   -   Product  -   PLC  -   H7 200SMART  -   Digital Module

EM DR32 Digital input/output module

Model no EM DR32 Article No H7 288-2DR32-0AA0 Description16 point digital input/16 point digital output relay type,Dimensions WxHxD(mm)72×100×81mm Power dissipatio10W

Model no

EM DR32

Article No

H7 288-2DR32-0AA0

Description

16-digital input/ 16-digital output, relay

Dimensions WxHxD(mm)

72×100×81mm
Product parameters Wiring diagram Relevant information
Specification parameters Model no

EM DR32

Article No H7 288-2DR32-0AA0
Description 16-digital input/ 16-digital output, relay
Conventional norm

Dimensions WxHxD(mm)

72×100×81mm
Power Consumption 10W
Current Consumption(SM bus) 180mA
Current Consumption(24V DC) 4mA for each input point used, each relay coil used is 11mA

Digital input

Number of Inputs

16
Type PNP/NPN(IEC  type 1 sinking)
Surge voltage (Maximum) 35VDC,lasting  0.5s
Logic 1 signal (Minimum) 15VDC
Logic 0 signal (Maximum) 5VDC
Optical Isolation (field side and  logic side) 500 V AC,lasting  1 min
Isolation group 2
Filter time 0.2,0.4,0.8,1.6,3.2,6.4,12.8ms(optional, 4 inputs form one group)
Number of Inputs that connect at the same time 16
Cable length (meter) 500M(Shield),150M(Unshielded)
Digital output

Number of Outputs

16
Type Relay
Voltage range 5~30V DC 5~250V AC
Surge voltage (Maximum) 7A when power on
Rated current foreach point(Maximum) 2.0A
Switching Delay from the disconnection to connection(Max): 50µs;
from the connection to disconnection(Max): 200µs
Optical Isolation(field side and logic side) 1500V AC, lasting 1 min(coils and contacts) ;none (coils and logic)
Isolation group 4
Output status in STOP mode Previous value or replacement value (default is 0)

Number of Inputs that connect at the same time 16
55° (horizontal) All
45° (vertical) All
Cable length (meter)

Shield

500M
Unshielded 150M