Model no
IM ET08Article No
E 288-9ET08-0AA0Description
Expansion rack module,6 smart series I/O modules can be extendedDimensions WxHxD(mm)
47×100×81mmPerfectly compatible with s7 200 Smart PLC
| Specification parameters | Model no |
IM ET08 |
| Article No | E 288-9ET08-0AA0 | |
| Description | Expansion rack module ,6 smart series I/O modules can be extended |
| Conventional norm |
Dimensions WxHxD(mm) |
47×100×81mm |
| Power Input Voltage | 20.4-28.8VDC | |
| Power Input Current | Only interface module:2mA; Maximum load: 1500mA | |
| Power Consumption | 2W | |
| 5V DC Backplane Current Supply | 1300mA, backplane current is continuously supplied |
| Communication Port |
Quantity |
2 |
| Electrical Type | RJ45(Not support polarity adaptation) | |
| Transmission Rate | 10 Mbit/s and 100Mbit/s | |
| Isolation or not | Yes(field and logic) |
| Digital Input |
Input Type |
Sinking/sourcing type (IEC type 1 sinking) |
| Number of Inputs | 4 | |
| Rated Voltage | 24V DC | |
| Surge Voltage(Max) | 35V DC, lasting 0.5s | |
| Logic 1 Signal (Min) | 15V DC | |
| Logic 0 Signal (Max) | 5V DC | |
| Input Delay(Max) | 4.5ms | |
| Optical Isolation (field side and logic side) | 500V AC, 1min |
| Digital Output | Output Type | Transistor output,Solid-MOSFET (Source type) |
| Number of Outputs | 4 | |
| Rated Voltage | 24V DC | |
| Voltage Range | 20.4-28.8V DC | |
| Rated Voltage | 8A,100ms | |
| Rated current per point (Max) | 0.75A | |
| Switching Frequency (Max) | - | |
| Switching Delay (Max) | 150µs | |
| Optical Isolation (field side and logic side) | 500V AC, 1min | |
| Contact Lifetime | ||
| .Non-loaded | - | |
| .Rated Load | - |
| Function Introduction | Overview | Ethernet interface module of H7-200Smart series transmits I/O data of I/O module expanded after interface module to master station through S7 slave protocol. Having following features: Up to 6 smart expansion modules can be expanded; Support S7, visiting I zone, Q zone, AI zone, AQ zone and V zone; It is convenient and efficient that S7 communication can be carried out with S7-200smart or H7-200smart series CPU through the S7 protocol (as the slave). |
| Supported Module Type | Support all digital and analog expansion modules (including I/O modules that use V zone), DP01 is not supported. |