Model no
CB 1241 RS485Article No
H7 241-1CH30-2XB0Description
Communication Signal Board – 2 Port RS485WxHxD(mm)
38×62×21 mm| Specification parameters | Model no | CB 1241 RS485 |
| Article No | H7 241-1CH30-2XB0 |
| Conventional norm | Dimensions WxHxD(mm) | 38×62×21mm |
| Weight | 40 g | |
| Type | RS485(2-wire half-duplex) | |
| Number of Ports | 2(RS485-0/RS485-1) | |
| Common-mode voltage range | -7 V to +12 V, 1 second; 3 Vrms continuous | |
| Transmitter differential output voltage | Min 2V when RL = 100Ω; min 1.5V when RL = 54Ω. | |
| Termination and biasing | 10k resistor from RS485-B0 to +5V 10k resistor from RS485-A0 to GND 10k resistor from RS485-B1 to +5V 10k resistor from RS485-A1 to GND |
|
| Optional terminals | none | |
| Receiver input impedance | Minimum 5.4 kΩ, including termination | |
| Receiver Threshold/Sensitivity | Minimum +/- 0.2V, typical hysteresis 60 mV | |
| Isolation | ||
| RS485 Signal and Chassis Ground | 707 V DC (Type Test) | |
| RS485 signal and CPU logiccommon terminal | ||
| Cable length, shielding | Maximum 1000 m | |
| Baud rate | 300 baud, 600 baud, 1.2 Kb, 2.4 Kb, 4.8 Kb, 9.6 Kb (default),19.2 Kb, 38.4 Kb, 57.6 Kb, 76.8 Kb, 115.2 Kb | |
| Paritycheck | None (default), Even, Odd, Mark (parity bit always set to 1), Space (parity bit always set to 0) | |
| Number of stop bits | 1 (default), 2 | |
| Flowcontrol | Not supported | |
| Waiting time | 0-65535ms | |
| Power loss | 1.5W | |
| Max current consumption (SM bus) | 300mA |