Model no | EM232 AO2× 12 | |
Article No | H7 232-0HB22-0XA0 | |
Description | 2-channel analog output; Resolution of 12 bits; Full channel support for current/voltage output |
Conventional | Dimensions WxHxD(mm) | 46×80×62 |
Power dissipatio | 2W | |
Available current(SM bus) | 40mA | |
Available current(Sensor power 24V) | 80mA |
Analog output | output path | 2 |
type | Voltage or current |
output range | current | 0-20mA |
Voltage | ±10V |
Data word format | Current output | 0~+32000 |
Voltage output | -32000~+32000 | |
Resolution | 11bit | |
Isolation(Field side and Logic side) | 500VAC,1min |
precision | Typical, 25° | ±0.5% full scale; |
Worst case, from 0 to 55 degrees | -±2% full scale |
Maximum Drive | Current output | 5k Ω maximum |
Voltage output | 500 Ω minimum |
file name