Model no | EM AR02 | |
Article No | E7 288-3AR02-0AA1 | |
Description | 2-channel thermal resistance temperature module, resolution 16 bits |
Conventional norm | Dimensions WxHxD(mm) | 47×100×81 |
Power dissipatio | 1.5W | |
Available current(SM bus 5V) | 120mA | |
Available current(Sensor power 24V) | 40mA |
Analog input | input path | 2 |
ScopeRated range (Data word) Overshoot/undershootrange(Data word) Upflow/underflow (Data word) | Please refer to the thermocouple selection table | |
Measure principle | Sigma-delta |
Resolution | Temperature | 0.1°C/0.1°F |
Supply voltage | 15+symbol bits | |
Max Operating Pressure | ±35V |
Isolate | Field side and Logic side | 500V AC |
Field sideand 24VDC side | 500V AC | |
24VDC sideand Logic side | 500V AC | |
Interchannel isolation | / | |
Common-moderejection | >120dB | |
Repeatability | 0.05%FS | |
Cold-end error | 0.5mW | |
Cable loopresistance(Maximum) | 20Ω, for Cu10, the maximum is 2.7Ω | |
Diagnose | Upflow/underflow;Operating signal range;24VDC low voltage | |
Cable length | 100m,Shielded twisted pair |
Suppressionfrequency selection | 400Hz(2.5ms) | |
60Hz(16.6ms) | ||
50Hz(20ms) | ||
10Hz(1000ms) |
file name
file description
Update date
operate