Model no | EM DR16 | |
Article No | E7 288-2DR16-0AA1 | |
Description | 8 point digital input/8 point digital output relay type |
Conventional norm | Dimensions WxHxD(mm) | 47×100×81mm |
Power dissipatio | 5.5W | |
Available current(SM bus 5V) | 145mA | |
Available current(Sensor power 24V) | Each input point used is 4mA,and each relay coil used is 11mA |
Digital input | input points | 8 |
Type | PNP/NPN(IEC 1 leakage type) | |
Surge voltage (Maximum) | 35VDC,Continue 0.5s | |
Logic 1 signal (Minimum) | 15VDC | |
Logic 0 signal (Maximum) | 5VDC | |
Isolate(Field sideand Logic side) | 500 V AC,Continue 1 min | |
Isolation group | 2 | |
Filtering time | 0.2,0.4,0.8,1.6,3.2,6.4,12.8ms(Optional, 4 in a group) | |
The number of inputsthat are connectedsimultaneously | 8 | |
Cable length (meter) | 500M(Shield),150M(Unshielded) | |
Digital output | Output points | 8 |
Type | Electric Relay | |
Voltage range | 5~30V DC 5~250V AC | |
Surge voltage (Maximum) | The contact is 7A when it’s closed | |
Rated current foreach point(Maximum) | 2.0A | |
On-off delay | The maximum duration ofdisconnect to connected is50us, and the maximumduration of connected todisconnected is 200us | |
Isolate (Field side andLogic side) | 1500V AC, lasting 1 min(coils and contacts) ;none (coils and logic) | |
Isolation group | 2 | |
Output status inSTOP mode | Previous or replacement value (default is 0) |
The number of inputs that are connectedsimultaneously | 8 | |
55° (horizontal) | All | |
45° (vertical) | All |
Cable length (meter) | Shield | 500M |
Unshielded | 150M |