Model no | SM 1223 DI 8x24 V DC DQ 8x24 V DC | |
Article No | H7 223-1BH32-0XB0 | |
Description | Digital value input/output module DI8 x 24VDC Drain type/source type andDQ8x 24VDC,Transistor type Output |
Conventional norm | Dimensions WxHxD(mm) | 45x100x75mm |
Power dissipatio | 2.5W | |
Available current(SM bus ) | 145mA | |
Available current(Sensor power 24V) | Input 4mA per point used |
Digital input | input points | 8 |
Type | Drain type/source type | |
Surge voltage | 35VDC,Continue 0.5s | |
Logic 1 signal (Minimum) | 2.5mA 15V DC | |
Logic 0 signal (Maximum) | 1mA 5V DC | |
Isolate(Field sideand Logic side) | 500 V AC,Continue 1 min | |
Isolation group | 2 | |
Filtering time | 0.2,0.4,0.8,1.6,3.2,6.4,12.8ms(Optional, 4 in a group) |
Digital output | Output points | 8 |
Type | Solid State -MOSFET(Source type) | |
Voltage range | 20.4 - 28.8V DC | |
Logic 1 signal at maximum current | Minimum 20V DC | |
Logic 0 signal with 10KΩ load | Maximum 0.1V DC | |
Electric current (Maximum) | 0.5A | |
Lamp load | 5W | |
Flood leakage current at each point | Maximum 10μA | |
Inrush current | 8A lasts up to 100ms | |
isolate(Field side and Logic side) | 500 V AC,Continue 1 min | |
Isolation group | 1 | |
Current at each common terminal(Maximum) | 4A | |
Time-delay switch | The maximum duration of disconnect to connected is 50us, and the maximum duration of connected to disconnected is 200us | |
Mechanical life (non-loaded) | / | |
Contact life at rated load | / | |
Behavior during RUN-STOP | Previous or replacement value (default is 0) |
file name
file description
Update date
operate