Model no | EM AR04 | |
Article No | H7 288-3AR04-0AA0 | |
Description | 4-channel thermal resistance temperature module, resolution 16 bits |
Conventional norm | Dimensions WxHxD(mm) | 47×100×81 |
Power dissipatio | 1.5W | |
Available current(SM bus 5V) | 120mA | |
Available current(Sensor power 24V) | 40mA |
Analog input | input path | 4 |
ScopeRated range (Data word) Overshoot/undershootrange(Data word) Upflow/underflow (Data word) | Please refer to the thermocouple selection table | |
Measure principle | Sigma-delta |
Resolution | Temperature | 0.1°C/0.1°F |
Supply voltage | 15+symbol bits | |
Max Operating Pressure | ±35V |
Isolate | Field side and Logic side | 500V AC |
Field sideand 24VDC side | 500V AC | |
24VDC sideand Logic side | 500V AC | |
Interchannel isolation | / | |
Common-moderejection | >120dB | |
Repeatability | 0.05%FS | |
Cold-end error | 0.5mW | |
Cable loopresistance(Maximum) | 20Ω, for Cu10, the maximum is 2.7Ω | |
Diagnose | Upflow/underflow;Operating signal range;24VDC low voltage | |
Cable length | 100m,Shielded twisted pair |
Suppressionfrequency selection | 400Hz(2.5ms) | |
60Hz(16.6ms) | ||
50Hz(20ms) | ||
10Hz(1000ms) |
Note: when choosing 400HZ filter, to maintain the resolution and accuracy of the module, the integration time should be 10ms.This option also suppresses noise at 100Hz and 200Hz.
file name
file description
Update date
operate