Model no | EM DR08 | |
Article No | H7 288-2DR08-0AA0 | |
Description | 8-point digitaloutput relay type |
Conventional norm | Dimensions WxHxD(mm) | 47×100×81mm |
Power dissipatio | 4.5W | |
Available current(SM bus 5V) | 120mA | |
Available current(Sensor power 24V) | Each relay coilused is 9mA |
Digital output | Output points | 8 |
Type | Electric Relay | |
Voltage range | 5~30V DC 5~250V AC | |
Surge voltage (Maximum) | The contact is 7Awhen it’s closed | |
Rated current foreach point(Maximum) | 2.0A | |
On-off delay | Up to 10ms | |
Isolate (Field side andLogic side) | 1500V AC, lasting 1 min(coils and contacts) ;none (coils and logic) | |
Isolation group | 2 | |
Output status inSTOP mode | Previous or replacement value (default is 0) |
Contact endurance | Non-loaded | 10000000 disconnect/close cycles |
Rated load | 100,000 disconnect/close cycles |
The number of inputs that are connectedsimultaneously | 8 | |
55° (horizontal) | All | |
45° (vertical) | All |
Cable length (meter) | Shield | 500M |
Unshielded | 150M |
file name
file description
Update date
operate